Case: T07FR02613

Parcel: 12801017J


Addresses:

1062 S WILMOT RD

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/06/2008 VIOL - BUILDING SVCS & SYSTEMS Approved all items corrected
12/27/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Unapproved conditions. Open junction boxes and open witing splices shall be prohibited. Approved covers shall be provided for all switches and outlet covers.

___ Provide covers for outlet by main entrance and junction box in ceiling of back office.
12/27/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

___ Remove extension cords.
12/27/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front o f electrical service equipment. Where the service equipment i swider than 30 inches, working space shall be no less than the width og the equipment. No storage of any kind shall be located within the designated working space.

___ Clear access to panel in storage shed.