Case: T07FR02613
Case Details
Entered Date:
12/27/2007
Applicant:
JOHNSON LEONARD G & DONNA R JT/RS
Description:
Fire Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02613
Case Description: INSPECTION
Total Completed Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2007 | VIOL - PRECAUTION AGAINST FIRE | BMERRITT | Approved | 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. ___ Remove combustibles from water heater closet. |
| 12/27/2007 | VIOL - FIRE RESIST.RATED CONST | BMERRITT | Approved | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. ___ Repair drywall in water heater closet. |
| 12/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | BMERRITT | Approved | 901.6.2 Records. Records of all systems inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. ___ Keep records on file for 3 years. |
| 12/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | BMERRITT | Approved | 901.6 Inspectino, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ___ Have all required extinguishers inspected, remove extinguishers that are not inspected. ___ Have fire sprinkler system inspected annually. |
| 12/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | BMERRITT | Approved | 605.3 Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front o f electrical service equipment. Where the service equipment i swider than 30 inches, working space shall be no less than the width og the equipment. No storage of any kind shall be located within the designated working space. ___ Clear access to panel in storage shed. |
| 12/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | BMERRITT | Approved | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ___ Remove extension cords. |
| 12/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | BMERRITT | Approved | 605.6 Unapproved conditions. Open junction boxes and open witing splices shall be prohibited. Approved covers shall be provided for all switches and outlet covers. ___ Provide covers for outlet by main entrance and junction box in ceiling of back office. |
| 12/27/2007 | VIOL - MEANS OF EGRESS | BMERRITT | Approved | 1027.3 Exit Sign illumination. Exit signs shall be internally or externally illuminated. 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or means of egress: 1. Group A having 50 or more occupants. ___ Fix/Replace Illuminated Exit signs and emergency lighting at Main, Southeast, and West Exits. |
| 12/27/2007 | INSP - FULL | BMERRITT | Approved | 1004.3 Posting of occupant load. Every room or space that is an assembly accupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ___ Provide Certificate of Occupancy **Owner/Manager in process of applying for CofO from city |
| 03/06/2008 | COMPL - REINSPECTION | BMERRITT | Approved | All items corrected |