Case: T07FR02553

Parcel: 133251840


Addresses:

8530 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
04/17/2008 VIOL - MOTOR FUEL DISPENSING Approved
12/21/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2206.6.2.6 Spill containers. A spill container having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to the tank and equipped with a manual drain valve that drains into the primary tank.

· The spill containers on the fill ports of the tanks must be tested for leaks and proper operation of the manual drain. If these fail they shall be repaired or replaced.
12/21/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2206.7.7.1 Leak detection. Where remote pumps are used to supply fuel dispensers, each pump shall have installed on the discharge side a listed leak detection device that will detect a leak in the piping and dispensers and provide an indication.

2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.
12/21/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times.

· The tank sumps shall be emptied of all liquids and inspected for damage.