Case: T07FR02508

Parcel: 12510003D


Addresses:

3501 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR02508

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/21/2008 VIOL - MEANS OF EGRESS Approved
12/14/2007 VIOL - MEANS OF EGRESS Partial Approval Doors were unlocked, but locks need to be changed.
12/10/2007 VIOL - MEANS OF EGRESS Violation Blocked exit:
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_______Clear exit area, and maintain it this way.
12/10/2007 VIOL - MEANS OF EGRESS Violation Locks on exits:

IFC2006 [TFC with modifications] / 1008.1.8.3 Locks and latches.
2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

Remove keyed locks from west bank of 4 doors. Replace padlock on security gate with a thumb turn bolt lock, or panic hardware.
You may be re-inspected for locked doors during business hours at anytime. Do not allow this to happen again.

Re-inspection date for items above scheduled on or after Dec. 31, 2007.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


__________________________I have received a copy of this inspection report.
Building Representative


_____________________________________________
Captain