Case: T07FR02443

Parcel: 10603121A


Addresses:

3344 N ORACLE RD

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
11/30/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 The hood extinguishing system nozzles shall be properly aligned with all cooking equipment.
NOTE: THe nozzles should be centered over the cooking equipment.
11/30/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.7 16 inches of space shall be maintained between all fryers and open flame cooking appliances.
11/30/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.77.6.3 Provide documentation of current hood cleaning.