Outstanding Inspections

Case Number: T07FR02443
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/30/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 The hood extinguishing system nozzles shall be properly aligned with all cooking equipment. NOTE: THe nozzles should be centered over the cooking equipment.
11/30/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.7 16 inches of space shall be maintained between all fryers and open flame cooking appliances.
11/30/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.77.6.3 Provide documentation of current hood cleaning.
11/30/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the double keyed lock from the north exit door located in the dinning area. NOTE: Replace the double keyed lock with a thumb turn lock.
11/30/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 The exit sign located in the kitchen shall be illuminated at all times.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02443
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/26/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.