Case: T07FR02436

Parcel: 140420900


Addresses:

6935 S TUCSON BL

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/29/2007 INSP - FULL Violation
11/29/2007 INSP - FULL Violation 315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.
Do not store materials 18 inches from celing.
11/29/2007 INSP - FULL Violation 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.

Remove romex hanging in Mgrs. office.
11/29/2007 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Remove any materials that block electrical panels. First floor laundry Rm., Panel in phone equipment room.
11/29/2007 INSP - FULL Violation 605.4 Multiplug adapters. Multiplug adaptors, such as cube
adaptors, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
605.4.1 Power tap design. Relocatable power taps shall be
of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed.
605.4.2 Power supply. Relocatable power taps shall be directly
connected to a permanently installed receptacle.
605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.
Do not piggy back power strips. Plug directly into approved power source.
11/29/2007 INSP - FULL Violation 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor cover-ings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
605.5.1 Power supply. Extension cords shall be plugged directly
into an approved receptacle, power tap or multiplug
adapter and, except for approved multiplug extension cords,
shall serve only one portable appliance.
Do not use extension cords for perminant wiring.
11/29/2007 INSP - FULL Violation 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason
shall be protected with approved methods capable of resisting
the passage of smoke and fire. Openings through fire-resistance-
rated assemblies shall be protected by self-closing or automatic-
closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barrier partitions
shall be maintained to prevent the passage of smoke and all
openings protected with approved smoke barrier doors or
leakage-rated (smoke) dampers.
Seal all holes in equipment rooms.
11/29/2007 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
Service extinguisher in elevator room.
11/29/2007 INSP - FULL Violation 912.4 Signs. A metal sign with raised letters at least 1 inch (25
mm) in size shall be mounted on all fire department connections
serving fire sprinklers, standpipes or fire pump connections.
Such signs shall read: AUTOMATIC SPRINKLERS or
STANDPIPES or TEST CONNECTION or a combination
thereof as applicable.
Identify Fire Dept. connections room. with sign.
11/29/2007 INSP - FULL Violation 3404.3.2 Liquid storage cabinets. Where other sections of
this code require that liquid containers be stored in storage
cabinets, such cabinets and storage shall be in accordance
with Sections 3404.3.2.1 through 3404.3.2.3.
Store Haz Mat materials in an approved storage cabinet.