Case: T07FR02436
Case Details
Entered Date:
11/29/2007
Applicant:
FIRST INN FRANCHISE INC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR02436
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Do not store materials 18 inches from celing. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 3404.3.2 Liquid storage cabinets. Where other sections of this code require that liquid containers be stored in storage cabinets, such cabinets and storage shall be in accordance with Sections 3404.3.2.1 through 3404.3.2.3. Store Haz Mat materials in an approved storage cabinet. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Remove romex hanging in Mgrs. office. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Remove any materials that block electrical panels. First floor laundry Rm., Panel in phone equipment room. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 605.4.1 Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. 605.4.3 Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. Do not piggy back power strips. Plug directly into approved power source. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cover-ings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. Do not use extension cords for perminant wiring. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance- rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly. 703.1.1 Fireblocking and draftstopping. Required fireblocking and draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction. 703.1.2 Smoke barriers. Required smoke barrier partitions shall be maintained to prevent the passage of smoke and all openings protected with approved smoke barrier doors or leakage-rated (smoke) dampers. Seal all holes in equipment rooms. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Service extinguisher in elevator room. |
| 11/29/2007 | INSP - FULL | JNAGORE | Violation | 912.4 Signs. A metal sign with raised letters at least 1 inch (25 mm) in size shall be mounted on all fire department connections serving fire sprinklers, standpipes or fire pump connections. Such signs shall read: AUTOMATIC SPRINKLERS or STANDPIPES or TEST CONNECTION or a combination thereof as applicable. Identify Fire Dept. connections room. with sign. |