Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.63 #1.Service and tag the kitchen hood extinguishing system. #2.Service and tag the sprinkler system. #3.Replace the missing FDC inlet covers for the sprinkler system. |
|
| 11/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 906.7 Mount the class K portable fire extinguisher located in the kitchen on a hanger. | |
| 11/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 903.4 Chain and lock the sprinkler system control valve in the open position. |