Description:

Full Fire Inspection.

Outstanding Inspections

Case Number: T07FR02261
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/08/2007 INSP - FULL JBURGE Correction Required Please correct the following Tucson Fire Code Violations:
11/08/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.63 #1.Service and tag the kitchen hood extinguishing system. #2.Service and tag the sprinkler system. #3.Replace the missing FDC inlet covers for the sprinkler system.
11/08/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.4 Chain and lock the sprinkler system control valve in the open position.
11/08/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Mount the class K portable fire extinguisher located in the kitchen on a hanger.
11/08/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Repair the emergency lighting unit located in the loading dock for the kitchen.