Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 10/12/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.6 Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switches and electrical outlet boxes |
| 10/12/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.5 extension cords and flexible cords shall not be a substitute for permanent wiring |
| 10/12/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.3 A working space of not less than 30 inces in width. 36 inces in depth and 78 inches in height shall be provided in front of electrical service equip. ( service panel on NW side ). |