Case: T07FR02069

Parcel: 10707005F

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/12/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switches and electrical outlet boxes
10/12/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 extension cords and flexible cords shall not be a substitute for permanent wiring
10/12/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 A working space of not less than 30 inces in width. 36 inces in depth and 78 inches in height shall be provided in front of electrical service equip. ( service panel on NW side ).