Case: T07FR02069
Case Details
Entered Date:
10/12/2007
Applicant:
SAIA MOTOR FREIGHT LINE INC
Description:
full inspection
Outstanding Inspections
Case Number: T07FR02069
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBEZEL | Correction Required | TFC 605.3 A working space of not less than 30 inces in width. 36 inces in depth and 78 inches in height shall be provided in front of electrical service equip. ( service panel on NW side ). |
| 10/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBEZEL | Correction Required | TFC 605.5 extension cords and flexible cords shall not be a substitute for permanent wiring |
| 10/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBEZEL | Correction Required | TFC 605.6 Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switches and electrical outlet boxes |
| 10/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBEZEL | Correction Required | TFC 901.6 Fire ext. shall be serviced annually and shall have current service tag attached. |
| 10/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBEZEL | Correction Required | TFC 906.7 Hand held port. fire ext. not housed in cabinets, shall be installed or brackets supplied |
| 10/12/2007 | VIOL - MEANS OF EGRESS | JBEZEL | Correction Required | TFC 1006.1 The means of egress including the means of discharge shall be illuminated at all times the building space served by the means of egress is occupied |
| 10/12/2007 | VIOL - MEANS OF EGRESS | JBEZEL | Correction Required | TFC 1008.1.8.3 Main exterior door or doors are permitted to be equipped with key operated locking devices from the egress side provided a readily visible sign is posted on the egress on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. |
| 10/12/2007 | VIOL - MEANS OF EGRESS | JBEZEL | Correction Required | TFC 1011.2 Exit signs shall be externally or internally illuminated at all times. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02069
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2007 | INSP - FULL | JBEZEL | Approved | Reinspection done 11/13/07. All conditions above corrected and approved. |