Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/12/2007

Applicant:

SAIA MOTOR FREIGHT LINE INC

Description:

full inspection

Outstanding Inspections

Case Number: T07FR02069
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
10/12/2007 VIOL - BUILDING SVCS & SYSTEMS JBEZEL Correction Required TFC 605.3 A working space of not less than 30 inces in width. 36 inces in depth and 78 inches in height shall be provided in front of electrical service equip. ( service panel on NW side ).
10/12/2007 VIOL - BUILDING SVCS & SYSTEMS JBEZEL Correction Required TFC 605.5 extension cords and flexible cords shall not be a substitute for permanent wiring
10/12/2007 VIOL - BUILDING SVCS & SYSTEMS JBEZEL Correction Required TFC 605.6 Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switches and electrical outlet boxes
10/12/2007 VIOL - FIRE PROTECTION SYSTEMS JBEZEL Correction Required TFC 901.6 Fire ext. shall be serviced annually and shall have current service tag attached.
10/12/2007 VIOL - FIRE PROTECTION SYSTEMS JBEZEL Correction Required TFC 906.7 Hand held port. fire ext. not housed in cabinets, shall be installed or brackets supplied
10/12/2007 VIOL - MEANS OF EGRESS JBEZEL Correction Required TFC 1006.1 The means of egress including the means of discharge shall be illuminated at all times the building space served by the means of egress is occupied
10/12/2007 VIOL - MEANS OF EGRESS JBEZEL Correction Required TFC 1008.1.8.3 Main exterior door or doors are permitted to be equipped with key operated locking devices from the egress side provided a readily visible sign is posted on the egress on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
10/12/2007 VIOL - MEANS OF EGRESS JBEZEL Correction Required TFC 1011.2 Exit signs shall be externally or internally illuminated at all times.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02069
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/13/2007 INSP - FULL JBEZEL Approved Reinspection done 11/13/07. All conditions above corrected and approved.