Case: T07FR02065

Parcel: 14029007D


Addresses:

3171 E VALENCIA RD

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/16/2007 INSP - FULL Correction Required October 16, 2007

Wendy's #401
3171 E. Valencia
85706-5950



Pre-Citation Notice

An inspection of the kitchen hood extinguishing system was conducted on 10/9/07 and found to be not in compliance. Currently a report dated 8/20/07 is indicating noncompliance. A report has been given to Rosie Cruz and Angela Norzagaray, managers at the Wendy's on 3171 E Valencia in Tucson, AZ.

A certificate of inspection was submitted and showed the system has failed inspection, this system is not being maintained properly. This is in violation of IFC 901.6.

You have until October 24, 2007 to properly maintain this kitchen hood system, or litigation shall be started.

If you have questions, or if I may be of any assistance please call me at 791-4502 extension 127.

Effrim Griffin
Fire Inspector
Tucson Fire Department
EG
cc: Bonita, CA
10/10/2007 INSP - FULL Violation Currently a non compliance tags are on required hood systems.
System shall be certified as compliance by 10-16-07.
Possible cease of cooking operations is no certification of complaince.