Case: T07FR02062

Parcel: 121050220


Addresses:

5548 E GRANT RD

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.4 Multiplug adapter at vending machine near deli shall not be used.
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cord at vending machine near deli shall not be used as permanent wiring.
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cords in second floor equipment room shall not be used as permanent wiring.
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Junction boxes located in the second floor equipment room shall have approved covers.
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cord located in the equipment room shall not be used as permanent wiring.
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 The electrical panels located in the stockroom at the west end shall have a 36 inch working space.
10/10/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 The electrical switch box in the stockroom at the west wall shall be secured to the wall.