Case: T07FR02062
Case Details
Entered Date:
10/10/2007
Applicant:
JLE WAY ASSOCIATES LIMITED PARTNERSHIP
Description:
Full Inspection
Outstanding Inspections
Case Number: T07FR02062
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Storage shall be removed from second floor equipment room. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The electrical switch box in the stockroom at the west wall shall be secured to the wall. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panels located in the stockroom at the west end shall have a 36 inch working space. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 Multiplug adapter at vending machine near deli shall not be used. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cord at vending machine near deli shall not be used as permanent wiring. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cord located in the equipment room shall not be used as permanent wiring. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords in second floor equipment room shall not be used as permanent wiring. |
| 10/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Junction boxes located in the second floor equipment room shall have approved covers. |
| 10/10/2007 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Ceiling tiles at front counter and 2nd floor office shall be replaced. |
| 10/10/2007 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Hole in celing at center of stockroom shall be repaired. |
| 10/10/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 Exit sign at office stairs shall be repaired. |
| 10/10/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 Exit sign at SE hallway shall be repaired. |
| 10/10/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 Exit sign in equipment room shall be repaired. |
| 10/10/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.2 Storage located on stockroom stairway shall be removed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02062
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2008 | INSP - FULL | TKNAPP | Approved |