Case: T07FR01992

Parcel: 10320084B

Inspection Status: Approved

Inspection History: INSP - LIFE SAFETY

Date Description Inspector Results Comments
12/27/2007 INSP - LIFE SAFETY Approved All noted Tucson Fire Code violations were corrected.
10/05/2007 INSP - LIFE SAFETY Not Applicable Alarm system problems. Inspectors test valve open and water flow alarm. Central alarm did not recieve notification of water flow and and alarm.
10/05/2007 INSP - LIFE SAFETY Not Applicable The alarm system is reading trouble in system ground fault. The FDC connections are stuck and wont swivel. The keys in the fire department lock box need to be changed.