Outstanding Inspections
Case Number: T07FR01992
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 506.2 Provide all necessary keys for fire department access to the riser rooms and fire alarm control panel room. |
| 10/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag the sprinkler systems. All systems. #2.Service and test the fire alarm system. #3.Repair the female coupling on all fire department connections. NOTE:They should swivel freely. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01992
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2007 | INSP - LIFE SAFETY | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |