Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | All O.K. | |
| 09/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ____Extension cords used to power equipment, lighting.2006 IFC 605.5 ***Replace ALL extension cords with UL approved power taps with overcurrent protection and circuit breakers. Piggybacking power taps is not allowed per 605.4.2. |
|
| 09/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ____unfused multiplug adapters in use. 2006 IFC 605.4 -Kitchen area. ***Replace multiplug adapter with approved power tap. |