| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Approved | ____unfused multiplug adapters in use. 2006 IFC 605.4 -Kitchen area. ***Replace multiplug adapter with approved power tap. |
| 09/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Approved | ____Extension cords used to power equipment, lighting.2006 IFC 605.5 ***Replace ALL extension cords with UL approved power taps with overcurrent protection and circuit breakers. Piggybacking power taps is not allowed per 605.4.2. |
| 09/18/2007 | VIOL - PRECAUTION AGAINST FIRE | BCORRALE | Approved | ____Storage underneath stairway. 2006 IFC 315.2.4 ***Remove all storage underneath stairway. |
| 09/18/2007 | VIOL - PRECAUTION AGAINST FIRE | BCORRALE | Approved | ____Storage in water heater enclosure. 2006 IFC 315.2.3 ***Remove storage from water heater enclosure. |
| 09/18/2007 | VIOL - PRECAUTION AGAINST FIRE | BCORRALE | Approved | ____Less than 2 ft. ceiling clearance in stockroom. 2006 IFC 315.2.1 ***Ensure at least a 2 ft. clearance from ceiling at all times. |
| 09/18/2007 | INSP - FULL | BCORRALE | Approved | On 9-13-07, a fire prevention inspection was conducted at 1317 S. 6th Ave. #139. Please correct the following Tucson Fire Code violations. All Code references are from the 2006 International Fire Code, with modifications. |
| 01/22/2008 | INSP - REINSPECTION | BCORRALE | Approved | All O.K. |