Inspection Status: Approved
Inspection History: VIOL - LIQUID PETROLEUM GASES
Case Number - T07FR01537
Inspection Description - VIOL - LIQUID PETROLEUM GASES
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/27/2007 | VIOL - LIQUID PETROLEUM GASES | Approved | Approved | |
08/09/2007 | VIOL - LIQUID PETROLEUM GASES | Correction Required | 3807.4 Protecting containers from vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in accordance with Section 312. | |
08/09/2007 | VIOL - LIQUID PETROLEUM GASES | Correction Required | 3804.3 Container location. Containers shall be located with respect to buildings, public ways, and lot lines of adjoining property that can be built upon, in accordance with Table 3804.3. - 501 to 2000 Gallon LPG containers shall be a minimum of ten feet from the above locations. |