Case: T07FR01537

Parcel: 121100020


Addresses:

4702 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T07FR01537

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2007 VIOL - MOTOR FUEL DISPENSING Approved Approved. All records in the file
09/10/2007 VIOL - MOTOR FUEL DISPENSING Approved The e-stop has been relocated.
Dispensing operations meet the setback requirements.
Veeder root report and annual Line leak and tank tightness test received.
08/09/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2207.4 Location of dispensing operations and equipment. In addition to the requirements of Section 2206.7, the point of transfer for dispensing operations shall be 25 feet (7620mm)or more from buildings having combustible exterior wall surfaces, buildings having noncombustible exterior wall surfaces that are not part of a 1-hour fire-resistance-rated assembly, or buildings having combustible overhangs, lot lines of property which could be built on, public streets, or sidewalks and railroads; and at least 10 feet (3048 mm) from driveways and buildings having noncombustible exterior wall surfaces that are part of a fire-resistance-rated assembly having a rating of 1 hour or more
- Provide documentation of the fire rated wall.
08/09/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2208.7 Emergency shutdown device. An emergency shutdown device shall be located within 75 feet (22 860 mm) of, but not less than 25 feet (7620 mm) from, dispensers, and shall also be provided in the compressor area. Upon activation, the emergency shutdown shall automatically shut off the power supply to the compressor and close valves between the main gas supply and the compressor and between the storage containers and dispensers.
- Relocate the emergency stop to be within guidelines.
08/09/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2206.2.1.1 Inventory control for underground tanks. Accurate daily inventory records shall be maintained and reconciled on underground fuel storage tanks for indication of possible leakage from tanks and piping. The records shall be kept at the premises or made available for inspection by the fire code official within 24 hours of a written or verbal request and shall include records for each product showing daily reconciliation between sales, use, receipts and inventory on hand. Where there is more than one system consisting of tanks serving separate pumps or dispensers for a product, the reconciliation shall be ascertained separately for each tank system. A consistent or accidental loss of product shall be immediately reported to the fire code official.
- Provide records of inventory control.
08/09/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.
- Provide documentation of the Veeder Root annual calibration.