Case: T07FR01537

Parcel: 121100020


Addresses:

4702 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T07FR01537

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2007 VIOL - PRECAUTION AGAINST FIRE Approved Bollards installed and approved
08/09/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required 312.2 Posts. Guard posts shall comply with all of the following requirements:
1. Constructed of steel not less than 4 inches (102 mm) in diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing of not less than a 15-inch (381 mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm) above ground.
5. Located not less than 3 feet (914 mm) from the protected object.