Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2007 | VIOL - PRECAUTION AGAINST FIRE | Approved | Bollards installed and approved | |
| 08/09/2007 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | 312.2 Posts. Guard posts shall comply with all of the following requirements: 1. Constructed of steel not less than 4 inches (102 mm) in diameter and concrete filled. 2. Spaced not more than 4 feet (1219 mm) between posts on center. 3. Set not less than 3 feet (914 mm) deep in a concrete footing of not less than a 15-inch (381 mm) diameter. 4. Set with the top of the posts not less than 3 feet (914 mm) above ground. 5. Located not less than 3 feet (914 mm) from the protected object. |