Case: T07FR01448

Parcel: 11310109B


Addresses:

2553 N CAMPBELL AV

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
08/01/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 #1.Service and tag the kitchen hood system.
#2.Service and tag the extinguisher,{RED}.
#3. The cooking equipment burners shall be in line with kitchen hood system nozzles.
08/01/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.5.2 A class K fire extinguisher shall be provided within a 30 foot travel distance of commercial-type cooking equipment.
08/01/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.6.3 Clean and remove all grease build-up from the kitchen hood system and cooking equipment.

A re-inspection is scheduled for 8/15/07.