Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/01/2007

Applicant:

COLSON EDWARD E III TR 16.66% & COLSON

Description:

Full fire inspection done by Inspector John Bieg on 8/1/07. "B".

Outstanding Inspections

Case Number: T07FR01448
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
08/01/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 The building address numbers shall comply with these requirements. {See the attached information.}
08/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag the kitchen hood system. #2.Service and tag the extinguisher,{RED}. #3. The cooking equipment burners shall be in line with kitchen hood system nozzles.
08/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5.2 A class K fire extinguisher shall be provided within a 30 foot travel distance of commercial-type cooking equipment.
08/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease build-up from the kitchen hood system and cooking equipment. A re-inspection is scheduled for 8/15/07.
08/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 #1.The north exit sign in the dining area shall be illuminated. #2.The south exit sign in the dining area shall be illuminated. #3.The exit sign located in the kitchen shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01448
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/06/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 9/5/07.