Case: T07FR01322

Parcel: 140420840


Addresses:

2520 E VALENCIA RD

Inspection Status: Continued

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
08/03/2007 VIOL - MEANS OF EGRESS Continued As of 2nd re-inspection the two slide bolt locks on the back exit door still remain in place... no correction made.
07/27/2007 VIOL - MEANS OF EGRESS Continued Sign on door over keylocking cylinder. Nothing else has been completed.
07/13/2007 VIOL - MEANS OF EGRESS Violation 4. IFC 1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. Remove two slide bolts from the rear kitchen exit.
07/13/2007 VIOL - MEANS OF EGRESS Violation 5. IFC 1008.1.8.3 Key bolt locking chylinder is permitted where a durable sign is conspicuously posted above the exit, in 1 inch letters, reading: " This door to remain unlocked when the building is occupied." You will place a sign above the rear kitchen exit or replace with a thumb bolt latch or panic hardware door.
07/13/2007 VIOL - MEANS OF EGRESS Violation 6. IFC 1011.2 Exit signs shall be internally or externally illuminated. Cause your two main exit signs and kitchen exit signs to be illuminated.