Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/13/2007

Applicant:

SCALETTA DOMINIC & GLORIA JT/RS

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR01322
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/03/2007 INSP - REINSPECTION NSPRENGE Continued No progress since the re - inspection on 7/27/07. Precitation will be sent out late this afternoon/ or early Monday by registered mail. Giving til 8/10/07 at noon to correct outstanding violations to avoid a citation being issued.
08/03/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Continued There has been nothing done to correct this problem as of 2nd re-inspection.
08/03/2007 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Continued As of 2nd re-inspection, nothing has been sent to show proof of inspection of commercial cooking system hood/ extinguishing system.
08/03/2007 VIOL - MEANS OF EGRESS NSPRENGE Continued As of 2nd re-inspection the two slide bolt locks on the back exit door still remain in place... no correction made.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01322
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/27/2007 VIOL - FIRE RESIST.RATED CONST NSPRENGE Approved correction has been made.