Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00989
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | All o.k. 6/15 | |
05/25/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Electrical panels blocked in rear stockroom.____ 605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. 2003 IFC ****Unblock, maintain panel access. |
|
05/25/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords in use (4), extension cords routed through ceiling in upstairs employee break room.____ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ****Remove extension cords, use approved power supplies. |