Case: T07FR00989

Parcel: 141148150


Addresses:

9050 E VALENCIA RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00989

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2007 VIOL - BUILDING SVCS & SYSTEMS Approved All o.k. 6/15
05/25/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical panels blocked in rear stockroom.____

605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. 2003 IFC
****Unblock, maintain panel access.
05/25/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords in use (4), extension cords routed through ceiling in upstairs employee break room.____

605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
****Remove extension cords, use approved power supplies.