Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00865
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2007 | VIOL - MEANS OF EGRESS | Approved | ||
05/02/2007 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. ______Install an emergency light to illuminate area and back door. |
|
05/02/2007 | VIOL - MEANS OF EGRESS | Violation | Exit signs: TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ______Place exit sign in an approved manner over the back door. [Paper will be ok- highly visible] |