Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00853
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2007 | VIOL - MEANS OF EGRESS | Approved | ||
05/02/2007 | VIOL - MEANS OF EGRESS | Violation | TFC 1027.6 [ammendment] Panic Hardware: Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. ______Remove keyed lock on rear door. |
|
05/02/2007 | VIOL - MEANS OF EGRESS | Violation | Keyed lock on front classroom door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove keyed lock, and replace with thumb-turn type. |
|
05/02/2007 | VIOL - MEANS OF EGRESS | Violation | 2 Exit signs not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit signs. |