Case: T07FR00853

Parcel: 12205003C

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00853

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/25/2007 VIOL - MEANS OF EGRESS Approved
05/02/2007 VIOL - MEANS OF EGRESS Violation TFC 1027.6 [ammendment] Panic Hardware:
Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

______Remove keyed lock on rear door.
05/02/2007 VIOL - MEANS OF EGRESS Violation Keyed lock on front classroom door:

1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove keyed lock, and replace with thumb-turn type.
05/02/2007 VIOL - MEANS OF EGRESS Violation 2 Exit signs not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix light in exit signs.