Case: T07FR00838

Parcel: 136210180


Addresses:

7450 E STELLA RD

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/30/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required The commercial kitchen hood extinguishing system was found to have been red tagged by the service company due to the bottle requiring a hydrstatic test.
04/30/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required The fire extinguisher found within 30' of the commercial kitchen extinguishing system is an ABC type and needs to be a "K" class extinguisher.
04/30/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required One of more portable fire extinguishers were found to have been last tested or service in 2003. Portable fire extinguishers shall be tested annually.