Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/30/2007

Applicant:

TUCSON SCHOOL DISTRICT NO 1

Description:

Routine Inspection

Outstanding Inspections

Case Number: T07FR00838
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/30/2007 VIOL - FIRE PROTECTION SYSTEMS wcummings Correction Required One of more portable fire extinguishers were found to have been last tested or service in 2003. Portable fire extinguishers shall be tested annually.
04/30/2007 VIOL - FIRE PROTECTION SYSTEMS wcummings Correction Required The commercial kitchen hood extinguishing system was found to have been red tagged by the service company due to the bottle requiring a hydrstatic test.
04/30/2007 VIOL - FIRE PROTECTION SYSTEMS wcummings Correction Required The fire extinguisher found within 30' of the commercial kitchen extinguishing system is an ABC type and needs to be a "K" class extinguisher.
04/30/2007 VIOL - MEANS OF EGRESS wcummings Correction Required Both side exits off of the rear stage were obstructed. All required / marked exits and exitways shall be free of all obstructions and at all times.
04/30/2007 VIOL - MEANS OF EGRESS wcummings Correction Required One or more of the emergency exit light assemblies was found to inoperative. Repair or replace as needed.
04/30/2007 VIOL - MEANS OF EGRESS wcummings Correction Required The south east exit out of the cafeteria was blocked by a table on the inside and a bench on the outside. All exits and exitways shall be free from all obstructions at all times.