Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 01/19/2007 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
The commercial kitchen fire extinguishing system requires a "K" class portable fire extinguisher within 30' of the appliances. |
| 01/19/2007 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
The manual pull station for the commercial litchen fire extinguishing system is obstructed from view and use by a large Hobart refridgerator. |
| 01/19/2007 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
The portable fire extinguishers shall be serviced annually. extinguishers were found that have not been serviced since 2002. |