Case: T07FR00764
Case Details
Entered Date:
04/21/2007
Applicant:
TUCSON SCHOOL DISTRICT NO 1
Description:
Routine Inspection
Outstanding Inspections
Case Number: T07FR00764
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 01/19/2007 | VIOL - PRECAUTION AGAINST FIRE | WCUMMING | Correction Required | Combustibles were being stored on or near electrical devices in the east basement area. |
| 01/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | WCUMMING | Correction Required | In the room behind door # 56 was an open electrical junction box. Replace the cover or repair as needed. |
| 01/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | The commercial kitchen fire extinguishing system requires a "K" class portable fire extinguisher within 30' of the appliances. |
| 01/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | The manual pull station for the commercial litchen fire extinguishing system is obstructed from view and use by a large Hobart refridgerator. |
| 01/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | The portable fire extinguishers shall be serviced annually. extinguishers were found that have not been serviced since 2002. |
| 01/19/2007 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | One or more emergency exit or exitway light assemblies were found to be inoperative. Repair or replace as needed. |
| 01/19/2007 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | One or more exit signs were found to be inoperative when the test button was activated. Repair or replace as needed. |