Case: T07FR00743

Parcel: 124040110


Addresses:

1435 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
02/08/2008 VIOL - MEANS OF EGRESS Approved all o.k.
04/26/2007 VIOL - MEANS OF EGRESS Violation Exit signs out in emergency mode.
-Dining room, east.____
-Foyer south entry way.____

1011.5.3 Power source. Exit signs shall be illuminated at all
times. To ensure continued illumination for a duration of not less
than 90 minutes in case of primary power loss, the sign illumination
means shall be connected to an emergency power system
provided from storage batteries, unit equipment or an on-site
generator.
****Repair Exit signs.
04/26/2007 VIOL - MEANS OF EGRESS Violation Storage in basement stairwell.____

1027.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use.
****Clear ALL storage from stairwells.
04/26/2007 VIOL - MEANS OF EGRESS Violation Panic hardware on exit doors not functioning.
-West T.V. room exit.____
-West courtyard exit.____

1008.1.8 Door operations. Except as specifically permitted by
this section egress doors shall be readily openable from the
egress side without the use of a key or special knowledge or effort.
1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code. 2003 IFC
***Repair panic hardware to ensure operation.