Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2008 | VIOL - MEANS OF EGRESS | Approved | all o.k. | |
| 04/26/2007 | VIOL - MEANS OF EGRESS | Violation | Exit signs out in emergency mode. -Dining room, east.____ -Foyer south entry way.____ 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. ****Repair Exit signs. |
|
| 04/26/2007 | VIOL - MEANS OF EGRESS | Violation | Storage in basement stairwell.____ 1027.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. ****Clear ALL storage from stairwells. |
|
| 04/26/2007 | VIOL - MEANS OF EGRESS | Violation | Panic hardware on exit doors not functioning. -West T.V. room exit.____ -West courtyard exit.____ 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code. 2003 IFC ***Repair panic hardware to ensure operation. |