Description:

Full Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00743
Case Description: INSPECTION
Total Completed Inspections - 10
End Date Description Inspector Results Comments
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved Smoke detector cover, battery, missing. Apt 26.____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ****Replace cover, battery, and test unit.
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved Smoke detector blocked by fabric decoration on wall. Apt. 22____ 901.8 Removal of or tampering with equipment. It shall be unlawful for any person to remove, tamper with or otherwise disturb any fire hydrant, fire detection and alarm system, fire suppression system, or other fire appliance required by this code except for the purpose of extinguishing fire, training purposes, recharging or making necessary repairs, or when approved by the fire code official. ****Remove decoration from ceiling. Keep ALL smoke detectors clear and unimpeded.
04/26/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved Extension cord in use to power microwave.____ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ****Replace with approved power source.
04/26/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved Multiplug adapter in House directors' entry closet.____ 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ****Replace with approved power source.
04/26/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved Lint buildup behind dryers in house.____ 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. ***Remove lint buildup from behind ALL clothes dryers in the house.
04/26/2007 VIOL - MEANS OF EGRESS BCORRALE Approved Panic hardware on exit doors not functioning. -West T.V. room exit.____ -West courtyard exit.____ 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code. 2003 IFC ***Repair panic hardware to ensure operation.
04/26/2007 VIOL - MEANS OF EGRESS BCORRALE Approved Storage in basement stairwell.____ 1027.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. ****Clear ALL storage from stairwells.
04/26/2007 VIOL - MEANS OF EGRESS BCORRALE Approved Exit signs out in emergency mode. -Dining room, east.____ -Foyer south entry way.____ 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. ****Repair Exit signs.
04/26/2007 INSP - FULL BCORRALE Approved On 4/20/07, a fire prevention inspection was conducted at 1435 E. 2nd Ave. Please correct the following Tucson Fire Code violations. All references are from the 2003 Intenational Fire code, with modifications.
02/08/2008 INSP - REINSPECTION BCORRALE Approved all o.k.