Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00739

Parcel: 11007414C


Addresses:

3989 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00739

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2007 VIOL - MEANS OF EGRESS Approved
04/18/2007 VIOL - MEANS OF EGRESS Violation Bolt locks:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

______Remove bolt locks on rear door.
04/18/2007 VIOL - MEANS OF EGRESS Violation Back door:
TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.

______Place above-mentioned sign on or near rear door in an approved manner.
04/18/2007 VIOL - MEANS OF EGRESS Violation Emergency lighting:
TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:

______Fix all inoperative emergency lights.