Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00739
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2007 | VIOL - MEANS OF EGRESS | Approved | ||
04/18/2007 | VIOL - MEANS OF EGRESS | Violation | Bolt locks: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove bolt locks on rear door. |
|
04/18/2007 | VIOL - MEANS OF EGRESS | Violation | Back door: TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ______Place above-mentioned sign on or near rear door in an approved manner. |
|
04/18/2007 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: ______Fix all inoperative emergency lights. |