Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00739
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
04/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved power strip. [office and game room] |
|
04/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Multiplug adapters: TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ______Remove noncomplying devices. [prize room] |
|
04/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Wall cover plates cracked and missing: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ Replace all broken and missing outlet cover plates: [N wall of game room and by the "Wheel of Fortune"] |