Case: T07FR00706

Parcel: 11007414C


Addresses:

3985 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00706

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/27/2007 VIOL - MEANS OF EGRESS Approved Exiting issues abated.
Note: Exit found blocked on 2 later re-inspections. Pre cited 6/21/2007.
04/11/2007 VIOL - MEANS OF EGRESS Violation Exit access, exit, and discharge path blocked:
1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other
emergency. Security devices affecting means of egress shall be subject to approval of the fire code official.

______ Clear exit path and keep it clear [36" minimum]
04/11/2007 VIOL - MEANS OF EGRESS Violation Bar on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_______Remove bar and all associated hardware from door.
04/11/2007 VIOL - MEANS OF EGRESS Violation Excessive force to open panic hardware door:
1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).

______ Have this door serviced to comply with this code.
04/11/2007 VIOL - MEANS OF EGRESS Violation Double door:
1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation.
Exception: More than one operation is permitted for unlatching doors in the following locations:
1. Places of detention or restraint.
2. Where manually operated bolt locks are permitted by
Section 1008.1.8.4. [2nd inactive leaf]

______ This door must have only one "thumb turn" lock on the active leaf, and NO Other locks, bolts, bars, etc. The other non- active leaf may have the slide bolts. You may NOT change this to a roll down security door unless you have the express written permission of Developmental Services [791-5550], as this door currently has an exit sign above it.
04/11/2007 VIOL - MEANS OF EGRESS Violation Exit signs not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix light in exit signs.