Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR00640
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
04/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | Scheduled | To be redone. | |
04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers not mounted by exits: TFC 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______Mount extinguisher[s] in an approved manner. |
|
04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Vents over bread warmer: 904.11.6.1 Ventilation system. The ventilation system in connection with hoods shall be operated at the re-quired rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. ______ Clean vents and associated hardware. Re-inspection date scheduled on or after April 25, 2007. If you have any questions or concerns please call me at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department ___________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |