Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00635

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2007 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 904.11.1 Pull ring for kitchen hood system shall be clear from obstructions at all times. Pull ring shall not be obstructed or obscured from view.
05/21/2007 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 906.5 Portable fire extinguishers shall be in conspicuuous locations and readily accessible. Extinguishers shall be installed on hangers or brakets.
04/05/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.5 Class "K" rated portable fire extinguisher shall beprovided within 30 feet travel distance and no less then 10 feet to cooking equipment.