Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00578
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.2 #1. The northwest exit access shall not be obstructed. #2. The rear/south exit shall not be obstructed. |
|
03/27/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1011.2 #1. The northwest exit sign shall be illuminated. Located above the exit sign. #2. The southwest exit sign shall be illuminated. Located above the exit. |
|
03/27/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 Remove the bar and other hardware used to lock the southwest exit door. | |
03/27/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8.3 The northwest exit door shall comply with this code. |