Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/27/2007

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire inspection done by inspector John Bieg 3-26-07. "M"/ Clothing store.

Outstanding Inspections

Case Number: T07FR00578
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
03/27/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove the storage from around the water heater located in the second floor west storage room.
03/27/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 The south storage rooms shall comply with this code.
03/27/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
03/27/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 Remove storage from blocking the riser pipe located in the southeast stock room.
03/27/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the orange extension cord located in the southeast storage room.
03/27/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 The electrical outlet located in the corridor by the rear exit shall have an approved cover.
03/27/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 #1. Replace all missing ceiling tiles located in the storage rooms. #2. Repair the hole in the wall located on the first floor in the east storage room. A re-inspection is scheduled for 4-9-07.
03/27/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the fire extinguisher located by the entrance to the southeast stock room. #2. Service and tag the fire extinguisher located by the west stairwell.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the bar and other hardware used to lock the southwest exit door.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The northwest exit door shall comply with this code.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The northwest exit sign shall be illuminated. Located above the exit sign. #2. The southwest exit sign shall be illuminated. Located above the exit.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 #1. The northwest exit access shall not be obstructed. #2. The rear/south exit shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00578
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/01/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/1/07. Inspector John Bieg.