Case: T07FR00397

Parcel: 13615018A

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/27/2007 VIOL - FIRE PROTECTION SYSTEMS Violation a fire started in a deap fat fryer. The fire was knoted down with a extingusher by the employee. En 13 extingushed the fire with a hose line, and call for a fire inspector.

IFC 901.6 Hood sys. must be maintained
Hood sys. failed to operate with the links fused. Sys. must be serviced and place back in service.
technison stated the co carrtige was punctured but did not fill the extingusher due to a blockage of the o-ring. The o-ring can block the discharge opening when the cartrige is srewed in to tight.
02/27/2007 VIOL - FIRE PROTECTION SYSTEMS Approved Hood system back in service 1300 2/27/07