Description:

fire inspection / grease fire, hood sys. failed

Outstanding Inspections

Case Number: T07FR00397
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
02/27/2007 VIOL - ADMINISTRATION SHIGGINB Violation IFC 2003 111.1 Stop work order. No cooking untill hood system is serviced and back on line. A full fire inspection is requiered after business is back operating again.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00397
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/27/2007 VIOL - FIRE PROTECTION SYSTEMS SHIGGINB Approved Hood system back in service 1300 2/27/07
02/27/2007 VIOL - FIRE PROTECTION SYSTEMS SHIGGINB Approved a fire started in a deap fat fryer. The fire was knoted down with a extingusher by the employee. En 13 extingushed the fire with a hose line, and call for a fire inspector. IFC 901.6 Hood sys. must be maintained Hood sys. failed to operate with the links fused. Sys. must be serviced and place back in service. technison stated the co carrtige was punctured but did not fill the extingusher due to a blockage of the o-ring. The o-ring can block the discharge opening when the cartrige is srewed in to tight.