Case: T07FR00397
Case Details
Entered Date:
02/27/2007
Applicant:
GOLF LINKS PANTANO LLC
Description:
fire inspection / grease fire, hood sys. failed
Outstanding Inspections
Case Number: T07FR00397
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | VIOL - ADMINISTRATION | SHIGGINB | Violation | IFC 2003 111.1 Stop work order. No cooking untill hood system is serviced and back on line. A full fire inspection is requiered after business is back operating again. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00397
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | Hood system back in service 1300 2/27/07 |
| 02/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | a fire started in a deap fat fryer. The fire was knoted down with a extingusher by the employee. En 13 extingushed the fire with a hose line, and call for a fire inspector. IFC 901.6 Hood sys. must be maintained Hood sys. failed to operate with the links fused. Sys. must be serviced and place back in service. technison stated the co carrtige was punctured but did not fill the extingusher due to a blockage of the o-ring. The o-ring can block the discharge opening when the cartrige is srewed in to tight. |