Case: T07FR00386

Parcel: 14113008H


Addresses:

9455 E RITA RD

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/12/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

The kitchen hood system baffles require routine cleaning to prevent the accumulation of grease.
02/12/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 912.6 Inspection, testing and maintenance. All fire department connections shall be periodically inspected, tested and maintained in accordance with NFPA 25.

The fire department hose connections are missing caps to prevent debris and obstructions from being placed in them. Replace the caps.