Case: T07FR00386
Case Details
Entered Date:
02/23/2007
Applicant:
VAIL SCHOOL DISTRICT NO 20
Description:
Routine Inspection
Outstanding Inspections
Case Number: T07FR00386
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 02/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. The kitchen hood system baffles require routine cleaning to prevent the accumulation of grease. |
| 02/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | 912.6 Inspection, testing and maintenance. All fire department connections shall be periodically inspected, tested and maintained in accordance with NFPA 25. The fire department hose connections are missing caps to prevent debris and obstructions from being placed in them. Replace the caps. |
| 02/12/2007 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise’s electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the device. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. Emergency lighting was found to be inoperable when the test buttons were pushed. Repair or replace as needed. |