Case: T07FR00385

Parcel: 14118007A


Addresses:

9950 E REES LP

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/14/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

It was noted that in several areas, large electrical transformers had combustible storage either on or near the equipment. This equipment produces heat and requires ventilation around it.