Inspection Status: Correction Required
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 305.1 Clearance from ignition sources. Clearance between ignition sources, such as light fixtures, heaters and flame-producing devices, and combustible materials shall be maintained in an approved manner. Gasoline containers were being stored in the 400 building mechanical room and propane cylinders were being stored in the MPR building mechanical room. This is a very dangerous situation as both these areas have or may have open flames or sparks at any time. These conditions were brought to the attention of the School Principal immediately. |