Inspection Status: Continued
Inspection History: INSP - AST/UST
| Date |
Description |
Inspector |
Results |
Comments |
| 02/13/2007 |
INSP - AST/UST |
|
Continued |
Tank was repaired as required. Dispensing pumps removed. Fuel line protected. placards replaced. Put into service 1400 on 02/13/07. |
| 02/12/2007 |
INSP - AST/UST |
|
Correction Required |
500 gallon AST for back-up generator on site. Needs emergency vent repaired, placards, nozzles locked out, security fence, protective sheath on hose to prevent tampering. |