Inspection History: INSP - AST/UST
Case Number - T07FR00314
Inspection Description - INSP - AST/UST
Inspection Status - Continued
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2007 | INSP - AST/UST | Continued | Tank was repaired as required. Dispensing pumps removed. Fuel line protected. placards replaced. Put into service 1400 on 02/13/07. | |
02/12/2007 | INSP - AST/UST | Correction Required | 500 gallon AST for back-up generator on site. Needs emergency vent repaired, placards, nozzles locked out, security fence, protective sheath on hose to prevent tampering. |