Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel in an approved manner. |
|
| 02/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Rewire light, Building 1, mechanical room. |
|
| 02/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.3.1 - Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. _____ Provide such signage. |