Case: T07FR00311

Parcel: 133146610


Addresses:

1200 N EL DORADO PL

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area in front of electrical panel in an approved manner.
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____ Rewire light, Building 1, mechanical room.
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3.1 - Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.

_____ Provide such signage.